14 DCMR § 14-507

VENTILATION OF BATHROOMS

In Force
Verified 10/26/2026 · Next check 11/2/2026
effective 3/8/1966District of ColumbiaMold, Asbestos & Indoor Air

Operative Text

14 DCMR § 14-507
507.1 Each bathroom shall be naturally or mechanically ventilated, at least equivalent to the requirements of this section.

507.2 Natural ventilation shall be provided by openings, other than a door, directly to the outside, the openable area of which is at least equal to five percent (5%) of the floor area of the room served.

507.3 No opening for ventilation of a bathroom shall contain less than two square feet (2 ft.2).

507.4 If mechanical ventilation is used, it shall provide for each bathroom with a single water closet outside air in a minimum quantity of one and one half cubic feet per minute per square foot of floor area (1½ ft.3/min./ft.2), with no recirculation permitted.

507.5 A bathroom having more than one water closet shall be provided with a minimum outside air quantity of two and one half cubic feet per minute per square foot of floor area (2½ ft.3/min./ft.2), with no recirculation permitted.

507.6 A mechanically ventilated bathroom shall not serve or open into any area that opens on, or is served by, a bathroom that is not similarly ventilated.
Source: Legislative text reproduced verbatim
Plain English

Under D.C. Mun. Regs. tit. 14 et seq. § 14-507, every bathroom in a residential dwelling must have adequate ventilation, achieved either through natural openings to the outside or through a mechanical system. Natural ventilation requires openings—other than doors—totaling at least 5% of the bathroom's floor area, with a minimum of 2 square feet. Mechanical systems must supply fresh outside air at specified rates depending on the number of water closets, and recirculation of air is not permitted under any mechanical setup.

Written by anthropic/claude-sonnet-4.6 · Reviewed on October 13, 2026

Plain English — not legal advice.

For Property Managers

Property owners and managers operating in the District of Columbia should ensure that every bathroom meets the ventilation standards set out in D.C. Mun. Regs. tit. 14 et seq. § 14-507. Compliant operators typically verify that natural ventilation openings meet both the 5% floor-area threshold and the 2-square-foot minimum, or that mechanical systems deliver the required outside-air flow rates—1.5 cubic feet per minute per square foot for single-water-closet bathrooms and 2.5 for those with more than one. Operators also confirm that mechanically ventilated bathrooms do not open into or serve adjacent areas that lack equivalent ventilation.

General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.

For Tenants

Tenants in the District of Columbia have a right to bathrooms that meet the ventilation standards established by D.C. Mun. Regs. tit. 14 et seq. § 14-507, which requires either adequate natural openings or a properly functioning mechanical system supplying fresh outside air. If a bathroom appears to lack sufficient ventilation—such as having no operable window or a non-functioning exhaust fan—tenants may document the condition and consider filing a complaint with the District's housing inspection authorities. Tenant-rights organizations in D.C. can provide general information about available enforcement paths, including how to raise a housing code violation.

General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.

Generated October 13, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.

Effective Timeline

Current
Mar 8, 1966
Click on timeline segments to view historical versions.

References Out

No outbound references recorded yet for this provision.

References In

Rules and statutes that cite this regulation

14 DCMR § 308
14 DCMR § 308
14 DCMR § 309
14 DCMR § 309.1
14 DCMR § 311
14 DCMR § 311.1
14 DCMR § 203
14 DCMR § 304
14 DCMR § 308.3
14 DCMR § 309.1

Related Rules

§ 6.13
OPEN BURNING PERMITS
§ 59
Ventilation for shafts
§ 200.946
§ 200.946 Building product standards and certification program for exterior finish and insulation systems, use of Materials Bulletin UM 101.

Source Information

Snapshot SHA:
Fetched:Oct 12, 2026, 09:02 PM UTC