East Rochester, N.Y., Code of Ordinances ch. 157 (eCode360 ed. 2026) § 157-7

Electrical requirements

In Force
Verified 11/10/2026 · Next check 12/10/2026
East RochesterCO & Smoke Alarms

Operative Text

East Rochester, N.Y., Code of Ordinances ch. 157 (eCode360 ed. 2026) § 157-7
Fire alarm systems shall: A. Be supplied with electrical energy from both a main source and from an auxiliary source, such as a battery supply or generator. If a generator is used as an auxiliary source, automatic transfer shall occur within 15 seconds of main power interruption. B. Have circuits for the transmission of alarms used only for fire protection. C. Have all wiring and equipment installed in accordance with Article 760, Fire Alarm Systems, National Electrical Code NFPA No. 70.
Source: Legislative text reproduced verbatim
Plain English

East Rochester, N.Y., Code of Ordinances ch. 157 § 157-7 establishes specific electrical standards for fire alarm systems in covered properties. These systems must draw power from both a primary source and a backup source—such as a battery or generator—with any generator-based backup switching over automatically within 15 seconds of a main power failure. Alarm transmission circuits must be dedicated solely to fire protection, and all wiring and equipment must conform to Article 760 of the National Electrical Code (NFPA No. 70).

Written by anthropic/claude-sonnet-4.6 · Reviewed on November 9, 2026

Plain English — not legal advice.

For Property Managers

Property owners and managers subject to ch. 157 § 157-7 generally ensure that fire alarm systems are connected to both a primary electrical supply and an approved auxiliary backup, verifying that any generator-based backup is configured for automatic transfer within the 15-second window the provision requires. Compliant operators also confirm that fire alarm transmission circuits are not shared with other systems, and that all wiring and equipment installations are documented as meeting Article 760 of NFPA No. 70. Routine inspections and records of qualified electrical work help demonstrate ongoing compliance with these requirements.

General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.

For Tenants

Tenants living in properties covered by East Rochester, N.Y., Code of Ordinances ch. 157 § 157-7 have an interest in knowing that their building's fire alarm system meets the dual-power-source and dedicated-circuit standards the provision sets out. If a fire alarm system appears to lack a functioning backup power source or shows signs of non-compliant wiring, tenants may report concerns to the local code enforcement or building inspection office in East Rochester. Tenant-rights organizations can help residents understand what documentation or inspections they may be entitled to request under local housing and fire-safety codes.

General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.

Generated November 9, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.

Effective Timeline

Click on timeline segments to view historical versions.

References Out

No outbound references recorded yet for this provision.

References In

No inbound references recorded yet for this provision.

Related Rules

§ 26C
Certain public accommodations; automatic smoke or heat detectors
§ 26D
Definitions applicable to Secs. 26D to 26F
§ 26E
Residential buildings or structures; installation of smoke detectors

Source Information

Snapshot SHA:
Fetched:Nov 9, 2026, 09:39 PM UTC