33A.09 - FIRE PROTECTION
All dwellings, dwelling units, roominghouses, rooming units, residential retreat centers, bed and
breakfasts, and tourist homes let for occupancy to another shall comply with the following
requirements:
(a) General. All buildings or portions thereof shall be provided with the degree of
fire-resistive construction, fire warning devices and fire extinguishing devices as
provided by this chapter and the Fire Code.
(b) Corridors. Corridors in apartment building serving an occupant load of ten or
more shall have walls and ceilings of not less than one-hour fire resistive
construction. Existing lath and plaster walls in good condition are permitted for
corridor walls and ceilings and for occupancy separations when approved by the
Building Official or Building Inspector.
(c) Corridor Doors. Doors located in a 1 hour fire-resistive corridor, not within a
dwelling unit, shall be a reasonably smoke and draft tight 1 ¾” solid core wood
door or a 20 minute fire-rated door assemble. Doors shall be self closing by
means of a door closure or a pair of spring loaded hinges and shall be
maintained so as to securely latch when closed by the closure or spring loaded
hinges.
(d) Openings in Corridors. Transom windows and openings other than doors are not
permitted into corridors unless they are a fixed one-hour fire-rated assembly
(e.g.fire rated glass) or have been covered with 5/8” type X gypsum board
applied to both sides of the transom. A smoke damper with a one-hour fire-
resistive rating shall protect ventilation ducts with openings into corridors.
(e) Smoke Detectors. Smoke detectors shall be installed as required by this
Section. A minimum of one detector shall be located in the basement and each
story. A detector shall be located outside of bedrooms in the immediate vicinity of
the bedrooms and inside each bedroom. Smoke alarms shall be installed 3 feet
or more horizontally from the door or opening of a bathroom that contains a
bathtub or shower unless this would prevent placement of a smoke alarm
required by this section. The Building Official or Building Inspector may require
additional smoke detectors where additional protection may be deemed
necessary.
Where more than one smoke alarm is required to be installed within an individual
dwelling unit, the alarm devices shall be interconnected in such a manner that
the actuation of one alarm will activate all of the alarms in the individual dwelling
unit. Physical interconnection of smoke alarms shall not be required where listed
wireless alarms are installed and all alarms sound upon activation of one alarm.
Chapter 33A – Page 19 Last updated 07/14/2021
CHAPTER 33A
EXCEPTION: Interconnection of smoke alarms in existing areas shall
not be required where alterations or repairs do not result in removal of
interior finishes exposing the structure.
Combination smoke and carbon monoxide alarms shall be permitted in lieu of
smoke alarms.
Smoke alarms installed in existing areas shall be permitted to be battery powered
provided any alterations or repairs do not result in the removal of interior wall or
ceiling finishes exposing the structure. If repairs or alterations will result in the
removal of interior wall or ceiling finishes and expose the structure, than the
smoke alarms shall receive their primary power from the building wiring where
such wiring is served from a commercial source and, where primary power is
interrupted, shall receive power from a battery.
The occupant of a dwelling or rooming unit must notify the building owner or
building manager within 24 hours of discovering that a detector is not functioning.
The building owner or manager shall take immediate action to render the
detector operational or replace it.
Any occupant, owner or manager of a dwelling or rooming unit who willfully
disables a smoke detector or causes it to be nonfunctioning is guilty of a
misdemeanor. If the unit is occupied by more than one tenant, each tenant shall
be held accountable.
(f) Carbon Monoxide Alarms. Carbon monoxide alarms shall be installed outside of
and not more than 10 feet from each separate sleeping area or bedroom. Alarms
shall be installed on each level containing sleeping areas or bedrooms. Where a
fuel-burning appliance is located within a bedroom or its attached bathroom, a
carbon monoxide alarm shall be installed within the bedroom.
Where more than one carbon monoxide alarm is required to be installed within
an individual dwelling unit, the alarm devices shall be interconnected in such a
manner that the actuation of one alarm will activate all of the alarms in the
individual dwelling unit. Physical interconnection of carbon monoxide alarms
shall not be required where listed wireless alarms are installed and all alarms
sound upon activation of one alarm.
EXCEPTION: Interconnection of carbon monoxide alarms in existing areas shall
not be required where alterations or repairs do not result in removal of interior
finishes exposing the structure.
Combination carbon monoxide and smoke alarms shall be permitted in lieu of
carbon monoxide alarms.
Carbon monoxide alarms installed in existing areas shall be permitted to be
battery powered provided any alterations or repairs do not result in the removal
of interior wall or ceiling finishes exposing the structure. If repairs or alterations
will result in the removal of interior wall or ceiling finishes and expose the
structure, than the carbon monoxide alarms shall receive their primary power
from the building wiring where such wiring is served from a commercial source
and, where primary power is interrupted, shall receive power from a battery.
Chapter 33A – Page 20 Last updated 07/14/2021
CHAPTER 33A
(g) Fire Alarm System. A fire alarm system meeting the requirements of the
Minnesota State Fire Code shall be installed in apartment buildings containing 16
or more dwelling units or exceeding 2 stories in height.
EXCEPTIONS:
1. A fire alarm system is not required in buildings not over two stories in
height where all dwelling units or sleeping units and contiguous attic and
crawl spaces are separated from each other and public or common areas
by at least 1-hour fire partitions and each dwelling unit or sleeping unit
has an exit directly to a public way, exit court or yard.
2. A fire alarm system is not required in buildings which are equipped
throughout with an approved automatic sprinkler system in accordance
with the Fire Code and the notification appliances will activate upon
sprinkler flow.
3. A fire alarm system is not required in buildings that do not have interior
corridors serving dwelling units and are protected by an approved
automatic sprinkler system installed in accordance with the Fire Code and
provided that dwelling units either have a means of egress door opening
directly to an exterior exit access that leads directing to the exits or are
served by open-ended corridors designed in accordance with the Fire
Code.
Fire alarm systems shall be tested in accordance with the procedures and
frequency required pursuant to the Minnesota State Fire Code and its
corresponding regulations, as the same may be amended from time to
time. Contractors who perform inspections, testing and/or maintenance
services on fire alarm systems or any other similar or related systems
within the City shall submit all compliant and non-compliant reports, and
such other reports and records, in accordance with and as required by the
Minnesota State Fire Code, to the Winona Fire Department using the
method approved by the Fire Chief. The method selected for filing
reports and records may include electronic or computer based reporting
or recording systems as determined by the Fire Chief.
(h) Fire Sprinkler Systems. A fire sprinkler system shall be installed in all new
apartment buildings, buildings converted into apartment buildings and in
apartment buildings during major renovations as required by the Fire Marshal,
and throughout all building with a Group R fire area in accordance with the
Building Code. Fire sprinkler systems shall be installed in accordance with the
Building Code and the Minnesota State Fire Code.
Fire sprinkler systems shall be tested in accordance with the procedures and
frequency required pursuant to the Minnesota State Fire Code and its
corresponding regulations, as the same may be amended from time to time.
Contractors who perform inspections, testing and/or maintenance services on fire
sprinkler systems or any other similar or related systems within the City shall
submit all compliant and non-compliant reports, and such other reports and
records, in accordance with and as required by the Minnesota State Fire Code, to
Chapter 33A – Page 21 Last updated 07/14/2021
CHAPTER 33A
the Winona Fire Department using the method approved by the Fire Chief. The
method selected for filing reports and records may include electronic or computer
based reporting or recording systems as determined by the Fire Chief.
(i) Fire Extinguishers. All rental units shall be equipped with a fire extinguisher with
a minimum rating of 2A 10BC. The extinguisher shall be located within the
individual dwelling unit or in a common hallway or corridor within 50 feet of the
dwelling unit door.
Fire extinguishers shall be serviced at least annually. A tag with the name of the
servicing company and the service date shall be affixed to the extinguisher and
shall remain affixed until the next servicing.
Ord. No. 3978 11/03/2014 Ord. No. 4063 12/18/2017 Ord. No. 4151 06/07/21Winona City Code Ch. 33A § 33A.09 establishes comprehensive fire protection requirements for all rental dwellings in the city, covering structural fire resistance, corridor construction, smoke detectors, carbon monoxide alarms, fire alarm systems, fire sprinkler systems, and portable fire extinguishers. Smoke and carbon monoxide alarms must be installed in specific locations, interconnected where multiple units are present, and kept operational; willfully disabling a smoke detector is classified as a misdemeanor. Larger apartment buildings face additional requirements, including full fire alarm systems and automatic sprinkler systems, with testing reports submitted to the Winona Fire Department.
Plain English — not legal advice.
Under § 33A.09, compliant rental property operators in Winona generally ensure that all required smoke detectors and carbon monoxide alarms are installed in the correct locations, interconnected as required, and promptly repaired or replaced within 24 hours of being notified of a malfunction. Operators of apartment buildings with 16 or more units or more than two stories typically maintain a fire alarm system meeting Minnesota State Fire Code standards and arrange for required testing, with reports submitted to the Winona Fire Department. Each rental unit is also equipped with a properly rated and annually serviced fire extinguisher (minimum 2A 10BC) bearing a current service tag, and corridor construction and doors meet the fire-resistive standards specified in § 33A.09(b) and (c).
General guidance for property managers — not legal advice for your specific situation. Consult an attorney for advice on your case.
Section 33A.09 of Winona's City Code gives tenants in rental housing the right to expect working smoke detectors, carbon monoxide alarms, and fire extinguishers maintained by the property owner or manager. If a smoke detector is found to be non-functioning, the provision requires tenants to notify the building owner or manager within 24 hours, after which the owner or manager must take immediate action to restore it — and willfully disabling a detector is a misdemeanor that can apply to tenants as well. Tenants who believe fire protection requirements are not being met may contact the City of Winona's building inspection office to report potential violations under § 33A.09, or consult a local tenant-rights organization for guidance on available options.
General guidance for tenants — not legal advice for your specific situation. Consult a tenant-rights organization or attorney for advice on your case.
Generated November 13, 2026 — auto-generated, not yet human-reviewed. See /transparency for methodology.
Effective Timeline
References Out
No outbound references recorded yet for this provision.
References In
No inbound references recorded yet for this provision.